PART 1 - GENERAL
| 1.1
|
Provide
all labor, equipment and materials to furnish and install prefabricated
portable steel building(s) where shown on the drawings. |
| 1.2
|
Related
work specified elsewhere |
| 1.2.1
|
Electrical
service supply and connection. |
| 1.2.2
|
Site/foundation
work. |
| 1.2.3
|
Unloading,
placement, installation and anchoring. |
| 1.2.4
|
Plumbing
& piping (if required). |
| 1.3
|
References
|
| 1.3.1
|
Prefabricated
building manufacturer shall provide the locations and owners
of 3 similar buildings that have been in service more than three
years so that the architect can inspect on site and obtain a
statement from the owners on the quality of workmanship (fit
and finish). |
| 1.4
|
Submittals
|
| 1.4.1
|
Upon award
of order, manufacturer shall prepare and submit shop drawings
for each different building required for this project. Drawings
shall include elevations, section, floor plan, electric schedule,
service entrance locations, and anchor clip detail. |
| 1.4.2
|
Color charts
illustrating available colors and patterns for specified finishes
shall be submitted to owner for prompt selections. |
| 1.5
|
Quality
assurance |
| 1.5.1
|
Structures
shall be the product of a manufacturer with a minimum of 20
years-documented experience in the design and fabrication of
portable steel buildings. |
| 1.5.2
|
The approved
manufacturer is Par-Kut International, Inc., 40961 Production
Drive, Harrison Township, Michigan, 48045, Phone (586) 468-2947,
Fax (586) 463-6059, website: www.parkut.com, email: sales@parkut.com.
|
| 1.5.3
|
Manufacturer
shall maintain and furnish proof of maintenance of quality assurance
program with regularly scheduled independent third party testing.
Production process will include 5-stage, 36-step inspection.
|
| 1.5.4
|
Prefabricated
buildings by manufacturers other than the one approved shall
submit sufficient data to enable approval to be given. As a
minimum: design drawings and/or calculations, applicable certifications,
catalog information, and color samples showing equal range of
variety. |
| 1.5.5
|
A request
for substitution must include a list of three or more projects
in satisfactory service for not less than three years that use
products identical to those being proposed for substitution.
For each project, provide name, address, and telephone number
of the A/E firm, the contractor and the owner. Requests for
substitution after bids have been submitted will not be considered.
|
| 1.5.6
|
Electrical devices factory installed
within the prefabricated building shall be UL listed. Factory installed wiring system shall
comply with the current NFPA’s National Electrical Code. |
| 1.5.7
|
Adherence
to applicable portions of state and local building codes is
the responsibility of the installing contractor. Building manufacturer
shall not be responsible for permits, special engineering calculations,
or architectural type drawings unless otherwise notified in
writing three weeks prior to release of bid document. |
| 1.5.8
|
Design
loads: Live Loads: Floor 50 PSF, roof 50 PSF, wind 100 MPH.
|
PART 2 - PRODUCTS
| 2.1
|
Short form
specification: Pre-assembled booth unit(s) shall be Model __________
PARVUE© (Model is determined by length first then width.
i.e. 6' x 8' booth is model 86 PARVUE©) as manufactured
by Par-Kut International, Inc. *Note: Minimum PARVUE© size
available is 3' x 6'. |
| 2.2
|
Structure:
Prefabricated steel building shall be single unit welded steel
construction with 14-gauge galvannealed steel panels and tubing
on the exterior and 18-gauge galvannealed steel interior panels.
Building to be shipped completely assembled. All welded joints
ground smooth. Aluminum or fiberglass construction not acceptable.
|
| 2.3
|
Base and
floor: Base height shall be 4 inches for outside use. Floor
shall be 12-gauge galvanized steel, 4-way tread plate. Four
1/4" steel angle iron anchor clips with pre-drilled holes are
provided to secure building. Anchors provided by installer shall
be galvanized or stainless steel. |
| 2.4
|
Door(s)
shall be top-suspended heavy duty sliding galvannealed steel,
18-gauge minimum, fully weather-stripped. Include Adams Riter
#1850 hook bolt type lock, view window and all roller assembly
hardware. Trolleys shall be ball bearing, adjustable pendant
type. |
| 2.5
|
Windows:
Shall be steel construction properly primed and finish painted.
All windows shall be fixed unless clearly stated otherwise.
Windows will have interior anodized aluminum stops screwed in
place for easy glass replacement, if required. Furnish glass
of type specified herein. Windows shall be squared and weather-sealed
at the factory. If sliding windows are required, provide sliding
windows as shown on drawings for ventilation and/or transaction
purposes. |
| 2.6
|
Glazing:
All windows and doors shall contain clear tempered safety glass,
1/4" minimum thickness. |
| 2.7
|
Finish: All interior and exterior
steel surfaces except rooftop and floor shall be painted with High Performance, Rust
Inhibitive, DuPont® Imron Polyurethane paint. Choice of single color paint as selected by
owner from Par-Kut’s standard colors. |
| 2.8
|
Canopy:
Shall be 14-gauge minimum galvanized steel and standard overhang
shall extend 6" beyond the walls. For buildings wider than 7
feet 6 inches, the standard overhang shall extend 3" beyond
the walls. Standard fascia height shall be 12". |
| 2.9
|
Roof: Provide
lifting ring(s) welded in roof for onsite lifting of unit. Roof
surface shall be 14-gauge galvannealed steel sheet. Roof seams
shall be continuously welded, caulked and weatherproofed. Roof
shall drain to downspout(s). |
| 2.10
|
Insulation:
Walls shall be insulated with 2" rigid fiberglass board, R=10.
Roof structure fully insulated, R=17.4. |
| 2.11
|
Work counter:
One 22" minimum depth 14-gauge painted steel counter across
width of booth mounted 32" above floor. Include one 16" wide
steel storage drawer. Counter shall be welded in place. Include
one electrical cord access hole install in counter above receptacle.
|
| 2.12
|
Electrical:
Unit shall be delivered complete with all wiring required for
fluorescent light with lamp and switch, one 110V duplex outlet, heater,
a 100A 12-circuit load center with branch circuit breakers and 100A
main breaker. All wiring copper #12 AWG minimum, enclosed in EMT.
All fittings, wiring devices and fixtures UL listed. Ready for site
connection. Three wire 240/120V single-phase service required. |
| 2.13
|
Heater:
Electrical wall heater shall be fan-forced type including integral
thermostat. Minimum heater size shall be 120V/1500W. (Specify
optional 208/240V units for larger buildings and cold climates.)
|
| 2.14 |
Optional
features: Provide items available from manufacturer's optional
equipment list at direction of owner/architect to best meet
site requirements. |
PART 3 - EXECUTION
| 3.1 |
General:
Install prefabricated buildings on flat and level concrete pad
in accordance with the manufacturer's recommendations and placement
drawings. Position units over utility stub-ups, verify building
is level and anchor. |
Par-Kut
reserves the right to improve these specifications without notice.
|
|
|