PART 1 - GENERAL
| 1.1
|
Provide
all labor, equipment and materials to furnish and install prefabricated
portable steel building(s) where shown on the drawings. |
| 1.2
|
Related
work specified elsewhere |
| 1.2.1
|
Electrical
service supply and connection. |
| 1.2.2
|
Site/foundation
work. |
| 1.2.3
|
Unloading,
placement, installation and anchoring. |
| 1.2.4
|
Plumbing
& piping (if required). |
| 1.3
|
References
|
| 1.3.1
|
Prefabricated
building manufacturer shall provide the locations and owners
of 3 similar buildings that have been in service more than three
years so that the architect can inspect on site and obtain a
statement from the owners on the quality of workmanship (fit
and finish). |
| 1.4
|
Submittals
|
| 1.4.1
|
Upon award
of order, manufacturer shall prepare and submit shop drawings
for each different building required for this project. Drawings
shall include elevations, section, floor plan, electric schedule,
service entrance locations, and anchor clip detail. |
| 1.4.2
|
Color charts
illustrating available colors and patterns for specified finishes
shall be submitted to owner for prompt selections. |
| 1.5
|
Quality
assurance |
| 1.5.1
|
Structures
shall be the product of a manufacturer with a minimum of 20
years-documented experience in the design and fabrication of
portable steel buildings. |
| 1.5.2
|
The approved
manufacturer is Par-Kut International, Inc., 40961 Production
Drive, Harrison Township, Michigan, 48045, Phone (586) 468-2947,
Fax (586) 463-6059, website: www.parkut.com, email: sales@parkut.com.
|
| 1.5.3
|
Manufacturer
shall maintain and furnish proof of maintenance of quality assurance
program with regularly scheduled independent third party testing.
Production process will include 5-stage, 35-step inspection.
|
| 1.5.4
|
Prefabricated
buildings by manufacturers other than the one approved shall
submit sufficient data to enable approval to be given. As a
minimum: design drawings and/or calculations, applicable certifications,
catalog information, and color samples showing equal range of
variety. |
| 1.5.5
|
A request
for substitution must include a list of three or more projects
in satisfactory service for not less than three years that use
products identical to those being proposed for substitution.
For each project, provide name, address, and telephone number
of the A/E firm, the contractor and the owner. Requests for
substitution after bids have been submitted will not be considered.
|
| 1.5.6
|
Electrical
devices factory installed within the prefabricated building
shall be UL listed. Factory installed wiring system shall bear
UL Classification label certifying compliance with the current
NFPA's National Electrical Code |
| 1.5.7
|
Adherence
to applicable portions of state and local building codes is
the responsibility of the installing contractor. Building manufacturer
shall not be responsible for permits, special engineering calculations,
or architectural type drawings unless otherwise notified in
writing three weeks prior to release of bid document. |
| 1.5.8
|
Design
loads: Live Loads: Floor 50 PSF, roof 50 PSF, wind 100 MPH.
|
PART 2 - PRODUCTS
| 2.1 |
1 Short
form specification: Pre-assembled booth unit(s) shall be Model
__________ CENTRY (Model is determined by length first then
width. i.e. 6' x 8' booth is model 86 CENTRY) as manufactured
by Par-Kut International, Inc. *Note: Minimum CENTRY size is
3' x 6'. |
| 2.2 |
Structure:
Prefabricated steel building shall be single unit welded steel
construction with 14-gauge galvannealed steel panels and tubing
on the exterior and 18-gauge galvannealed steel interior panels.
Building to be shipped completely assembled and include 3"
radius corners. All welded joints ground smooth. Aluminum or
fiberglass construction not acceptable. |
| 2.3 |
Base and
floor: Base height shall be 4 inches for outside use. Floor
shall be 12-gauge galvanized steel, 4-way tread plate. Four
1/4" steel angle iron anchor clips with pre-drilled holes
are provided to secure building. Anchors provided by installer
shall be galvanized or stainless steel. |
| 2.4 |
Door(s)
shall be top-suspended heavy duty sliding galvannealed steel,
18-gauge minimum, fully weather-stripped. Include Adams Riter
#1850 hook bolt type lock, view window and all roller assembly
hardware. Trolleys shall be ball bearing, adjustable pendant
type. |
| 2.5 |
Windows:
Shall be steel construction properly primed and finish painted.
All windows shall be fixed unless clearly stated otherwise.
Windows will have interior 3/4" x 3/4" anodized aluminum
stops screwed in place for easy glass replacement, if required.
Furnish glass of type specified herein. Windows shall be squared
and weather-sealed at the factory. If sliding windows are required,
provide sliding windows as shown on drawings for ventilation
and/or transaction purposes. |
| 2.6 |
Glazing:
All windows and doors shall have square corner window openings
and contain clear tempered safety glass, 1/8" minimum thickness. |
| 2.7 |
Finish:
All steel surfaces shall be painted with rust inhibitive epoxy
primer. All exposed interior and exterior steel surfaces shall
be painted with one finish coat of industrial acrylic epoxy.
Choice of single color of paint as selected by owner from manufacturer's
standards. |
| 2.8 |
Canopy:
Shall be 14-gauge minimum galvannealed steel and standard overhang
shall extend 3" beyond the walls. Standard fascia height
shall be 8". Canopy to have radius corners, equal to the
amount of roof overhang. |
| 2.9 |
Roof: Provide
lifting ring(s) welded in roof for onsite lifting of unit. Roof
surface shall be 14-gauge galvannealed steel sheet. Roof seams
shall be continuously welded, caulked and weatherproofed. Roof
shall drain to downspout(s). |
| 2.10 |
Insulation:
Walls shall be insulated with 2" rigid fiberglass board,
R=10. Roof structure fully insulated, R=17.4. |
| 2.11 |
Work counter:
One 14-gauge painted steel counter across width of booth mounted
32" above floor. Include one 16" wide steel storage
drawer. Counter shall be welded in place. Include one electrical
cord access hole install in counter above receptacle. |
| 2.12 |
Electrical:
Unit shall be delivered complete with all wiring required for
two-lamp shielded fluorescent light with lamps and wall switch,
one 110V duplex outlet, heater, a 100A 12-circuit load center
with branch circuit breakers and 100A main breaker. All wiring
copper No. 12 minimum, enclosed in EMT. All fittings, wiring
devices and fixtures UL listed. Ready for site connection. Three
wire 240/120V single-phase service required. |
| 2.13 |
Heater:
Electrical wall heater shall be fan-forced type including integral
thermostat. Minimum heater size shall be 120V/1500W. (Specify
optional 208/240V units for larger buildings and cold climates.) |
| 2.14 |
Optional
features: Provide items available from manufacturer's optional
equipment list at direction of owner/architect to best meet
site requirements. |
PART 3 - EXECUTION
| 3.1 |
General:
Install prefabricated buildings on flat and level concrete pad
in accordance with the manufacturer's recommendations and placement
drawings. Position units over utility stub-ups, verify building
is level and anchor. |
Par-Kut
reserves the right to improve these specifications without notice.
|
|
|